PT100, PTC and Thermocouple Sensors and Accessories

Tecsystem supplies the full range of sensors and accessories behind every temperature control unit we make: Pt100 RTD probes in four insulation types, PTC and thermocouple sensors, extension cables, sensor wiring boxes and simulators for commissioning and testing.

Talk to our technical team Download the full datasheet library

RTD vs. thermocouple vs. PTC: choosing the right sensor type

The three sensor technologies aren't interchangeable. A Pt100 RTD gives a precise, linear reading and is the standard choice for winding and oil temperature monitoring on Tecsystem's PT100-input controllers (T154, T1048, NT935 and others). A PTC sensor reacts at a fixed threshold rather than reporting a continuous value, which is why it pairs with simpler protection units like the T30 and T119. A type K thermocouple reads far higher temperatures than either — up to 750°C — making it the right choice for oven and furnace applications, or the windings of oil power transformers.

Pt100 sensors

Four Pt100 variants, differentiated by insulation material, temperature rating and accuracy class — matched to where and how the sensor is installed.

SensorMax temperatureClassApplicationCap/jacket material
PTSW200°C (short-term 220°C)BGeneral winding embedmentSilicone rubber, PPS cap
PTSPW180°CAHigher-accuracy winding monitoringFEP jacket, fibreglass cap
PTFEW220°CAHigher-temperature, high-accuracy monitoringTeflon PFA
PTO250°C (reading range)—Oil transformers — threaded probe, DIN B headStainless steel probe, 3/4" or 1/2" gas thread
Explore PTSW Explore PTSPW Explore PTFEW Explore PTO

PTSW, PTSPW and PTFEW are supplied in standard cable lengths from 1m to 25m depending on model; PTO is a threaded probe (100–200mm probe length) built for direct mounting into an oil transformer body rather than winding embedment.

PTC and thermocouple sensors

PTC — winding temperature sensor

A fast-response PTC sensor compliant with DIN 44081/44082, for detecting winding temperature on electric motors or transformers. Intervention temperature 60–190°C, PTFE cable (3m standard, other lengths on request), 3mm sensor diameter.

TCK — type K thermocouple

A Cr-Al thermocouple for high-temperature applications such as oven monitoring, with a compression fitting (1/4" gas) and compensated type K cable. Maximum operating temperature 750°C, available in straight (Type A) or 90° (Type B) configurations.

Simulators for commissioning and testing

Both simulators let you verify a control unit's correct operation without connecting it to a live transformer or motor — replacing the sensor with the simulator's terminal and adjusting temperature values via potentiometer or toggle switches, including simulating sensor faults such as short circuit or open circuit.

PT100 Simulator

Simulates temperatures from 0°C to 266°C across configurable and fixed channels, with dedicated fixed-value channels at 48°C and 124°C for quick verification.

PTC Simulator

Simulates 3 PTC output lines (FAN-L1-L2), designed to connect directly to T119 and T119 DIN units via a dedicated 4-pole terminal.

Extension cables

Choose the extension cable by operating temperature and required dielectric strength — the higher-rated cables (CTES, CTFEW-compatible) are built for applications closer to the sensor's own maximum rating rather than general-purpose wiring.

Cable Max temperature Dielectric strength Outer diameter
CTSW 200°C 2 kVac / 5 kVac 3.6 mm
CTES 220°C 5000 Vac 5.2 mm
CTSE 90°C 2000 Vac 12 mm

Explore CTSW Explore CTES

Sensor wiring boxes

SCS wiring boxes provide the junction point between sensors installed inside the transformer and the extension cable running to the control unit, available in polyamide or aluminium housings depending on the operating environment.

Box materialWorking temperatureCable glandTerminal wire section
Polyamide (RAL7001)-20°C to +120°CPG160.25–1.5 mm²
Aluminium (RAL7040)-40°C to +120°CPG16-PG210.25–1.5 mm²

SCS-R 3/4 and SCS-R 6/8 share the same box and terminal specifications; the two versions differ in the number of sensor channels wired (3–4 vs. 6–8 sensors per box).

Explore SCS-R 3/4 Explore SCS-R 6/8

Surge protection for control units

PT73 protects a Tecsystem control unit from voltage surges and fluctuations on the 230 Vac supply — particularly effective at cutting the voltage spike generated when an MV switch closes, thanks to a built-in turn-on delay (adjustable 1–5 seconds). DIN-rail mounted, with a red LED indicating fuse intervention.

Explore PT73

Choosing the right sensor

Need Recommended product
Standard winding embedment, general use PTSW
Higher accuracy, moderate temperature PTSPW
Higher accuracy, higher temperature PTFEW
Oil transformer, threaded probe mounting PTO
Simple threshold-based protection (T30, T119) PTC
Furnace/oven, very high temperature TCK
Commissioning and fault simulation PT100 Simulator / PTC Simulator
Voltage surge protection on the control unit PT73
Remote 4-20mA output See AD-suffix control units

Built for demanding environments

Sensor insulation materials are selected for the application: silicone rubber and FEP for standard winding embedment, PTFE/Teflon for higher-temperature and higher-dielectric applications. Wiring boxes are rated IP-appropriate for their housing material, and all sensors are calibrated to IEC 60751:2022 where applicable.

Frequently asked questions

What's the difference between a PTSW and a PTFEW sensor?

Both are Pt100 3-wire sensors, but PTFEW uses a Teflon PFA jacket rated to 220°C and Class A accuracy, while PTSW uses a silicone rubber jacket rated to 200°C and Class B accuracy. PTFEW is the choice where either higher temperature or higher accuracy is required.

Can I use a Pt100 sensor on an oil transformer?

Yes, but use the PTO variant rather than PTSW/PTSPW/PTFEW — PTO is built as a threaded stainless steel probe (DIN B head, 3/4" or 1/2" gas thread) designed for direct mounting into the transformer body, rather than a cable-end sensor for winding embedment.

Do you offer a temperature transmitter with 4-20mA output?

Not as a standalone sensor accessory — the 4-20mA output is built into our AD-suffix control units (NT935 AD, NT538 AD, MM453 AD and others), which take a Pt100 or PTC sensor as input and provide the analog transmitter output alongside RS485 Modbus. See our connectivity and data management page for the full list.

What's the maximum extension cable length for a Pt100 sensor?

It depends on the cable: CTSW is rated for up to 100m; most Tecsystem control units also specify cable compensation up to 500m (1mm² section) directly in their own input specifications, so the practical limit is usually set by the controller rather than the cable itself.

Not sure which sensor or accessory fits your application?

Our technical team can help you match the right sensor, cable and wiring box to your control unit and installation environment.

Contact our technical team Browse the full product catalogue